已收录 268921 条政策
 政策提纲
  • 暂无提纲
EVALUATION OF FIRE HAZARDS WHILE REPACKAGING PLUTONIUM-CONTAMINATED SCRAP IN HB-LINE
[摘要] The potential for a fire while repackaging plutonium-contaminated scrap was evaluated. The surface-to-mass ratio indicates the metal alone will not spontaneously ignite. Uranium hydride can form when uranium metal is exposed to water vapor or hydrogen; uranium hydride reacts rapidly and energetically with atmospheric oxygen. The plutonium-contaminated scrap has been inside containers qualified for shipping, and these containers are leak-tight. The rate of diffusion of water vapor through the seals is small, and the radiolytic hydrogen generation rate is low. Radiography of samples of the storage containers indicates no loose oxide/hydride powder has collected in the storage container to date. The frequently of a fire while repackaging the plutonium-contaminated scrap is extremely unlikely.
[发布日期] 2003-12-18 [发布机构] Savannah River Site (S.C.)
[效力级别]  [学科分类] 
[关键词] Fire Hazards;Diffusion;08 Hydrogen;Water Vapor;Scrap [时效性] 
   浏览次数:10      统一登录查看全文      激活码登录查看全文