已收录 273503 条政策
 政策提纲
  • 暂无提纲
STEADY STATE FLAMMABLE GAS RELEASE RATE CALCULATION AND LOWER FLAMMABILITY LEVEL EVALUATION FOR HANFORD TANK WASTE
[摘要] This report assesses the steady state flammability level under off normal ventilation conditions in the tank headspace for 28 double-shell tanks (DST) and 149 single shell-tanks (SST) at the Hanford Site. Flammability was calculated using estimated gas release rates, Le Chatelier's rule, and lower flammability limits of fuels in an air mixture. This revision updates the hydrogen generation rate input data for all 177 tanks using waste composition information from the Best Basis Inventory Detail Report (data effective as of August 4,2008). Assuming only barometric breathing, the shortest time to reach 25% of the lower flammability limit is 11 days for DSTs (i.e., tank 241-AZ-10l) and 36 days for SSTs (i.e., tank 241-B-203). Assuming zero ventilation, the shortest time to reach 25% of the lower flammability limit is 10 days for DSTs (i.e., tank 241-AZ-101) and 34 days for SSTs (i.e., tank 241-B-203).
[发布日期] 2009-10-26 [发布机构] 
[效力级别]  [学科分类] 核能源与工程
[关键词] AR FACILITIES;EVALUATION;FLAMMABILITY;VENTILATION;STORAGE FACILITIES;RADIOACTIVE WASTES;DEGASSING;HANFORD RESERVATION;LIMITING VALUES [时效性] 
   浏览次数:25      统一登录查看全文      激活码登录查看全文