The Researching on Evaluation of Automatic Voltage Control Based on Improved Zoning Methodology
[摘要] According to the present serious phenomenon of increasing size and structure of power system, hierarchically structured automatic voltage control(AVC) has been the researching spot. In the paper, the reduced control model is built and the adaptive reduced control model is researched to improve the voltage control effect. The theories of HCSD, HCVS, SKC and FCM are introduced and the effect on coordinated voltage regulation caused by different zoning methodologies is also researched. The generic framework for evaluating performance of coordinated voltage regulation is built. Finally, the IEEE-96 stsyem is used to divide the network. The 2383-bus Polish system is built to verify that the selection of a zoning methodology affects not only the coordinated voltage regulation operation, but also its robustness to erroneous data and proposes a comprehensive generic framework for evaluating its performance. The New England 39-bus network is used to verify the adaptive reduced control models' performance.
[发布日期] [发布机构] State Power Research Institute of Chongqing Electric Power Company, Chongqing; 421120, China^1
[效力级别] 无线电电子学 [学科分类]
[关键词] Automatic voltage control;Control model;Erroneous datum;Generic frameworks;New England;Power System [时效性]