Pre-charging Characteristics Analysis and Control Strategy of Full Bridge MMC-HVDC
[摘要] Considering the FB-MMC, a generalized pre-charging strategy is proposed for the MMC-based systems. It contains two stages, no control charging and controllable charging. The circuit model of the converter is established in the no control charging stage, and the submodule capacitance can be charged to about 37% of rated voltage. During the controllable charging stage, we proposed grouping charging strategy, the blocked and bypassed strategy of each group sub-module is formulated. According to the circuit model, the capacitance voltage of each module can be charged to the rated value through this strategy. Finally, we set up a 9 level full bridge MMC-HVDC simulation system in PSCAD/EMTDC. The charging strategies are simulated, and the results show that the proposed control strategy is feasible.
[发布日期] [发布机构] Smart Power Grid Shaanxi Key Laboratory, Xi'An Jiaotong University, Xi'an; 710049, China^1;Xi'An XD Power System Co. Ltd, Xi'an; 710065, China^2
[效力级别] 电工学 [学科分类]