Zone Model Plume Algorithm Performance
[摘要] References(31)Four plume algorithms used by three zone type building fire simulators are evaluated against experiential data of Steckler and Nakaya. Significant differences in the room flow predictions are found with even the best performing plume algorithms predicting flows well below the measured values. Differences in plume behavior is attributed to (1) the background noise (turbulence) present when the data used in formulating the algorithms was collected, and (2) the inability of the plume algorithms to easily simulate the effect of plume blowing.The behavior of the McCaffrey plume in situations were the over-fire region dominates the plume flow is discussed.
[发布日期] [发布机构]
[效力级别] [学科分类] 环境科学(综合)
[关键词] Room fires;Plumes;Zone fire models [时效性]