Performance evaluation of wet-cooling tower fills with computational fluid dynamics
[摘要] ENGLISH ABSTRACT: A wet-cooling tower fill performance evaluation model developed by Reuter is derived in Cartesian coordinates for a rectangular cooling tower and compared to cross- and counterflow Merkel, e-NTU and Poppe models. The models are compared by applying them to a range of experimental data measured in the cross- and counterflow wet-cooling tower test facility at Stellenbosch University. The Reuter model is found to effectively give the same results as the Poppe method for cross- and counterflow fill configuration as well as the Merkel and e-NTU method if the assumptions as made by Merkel are implemented. A second order upwind discretization method is applied to the Reuter model for increased accuracy and compared to solution methods generally used to solve cross- and counterflow Merkel and Poppe models. First order methods used to solve the Reuter model and crossflow Merkel and Poppe models are found to need cell sizes four times smaller than the second order method to obtain the same results. The Reuter model is successfully implemented in two- and three-dimensional ANSYS-Fluent® CFD models for under- and supersaturated air. Heat and mass transfer in the fill area is simulated with a user defined function that employs a second order upwind method. The two dimensional ANSYS-Fluent® model is verified by means of a programmed numerical model for crossflow, counterflow and cross-counterflow.
[发布日期] [发布机构] Stellenbosch University
[效力级别] [学科分类]
[关键词] [时效性]