Steam flow distribution in air-cooled condenser for power plant application
[摘要] ENGLISH ABSTRACT: Air-cooled steam condensers are used in arid regions where adequate cooling water is not available or very expensive. In this thesis the effect of steam-side and air-side effects on the condenser performance, steam distribution and critical dephlegmator length is investigated for air-cooled steam condensers as found in power plants. Solutions are found so that no backflow is present in the condenser. Both single and two-row condensers are investigated.The tube inlet loss coefficients have the largest impact on the critical dephlegmator tube length in both the single and two-row condensers. The critical dephlegmator tube lengths were determined for different dividing header inlet geometries and it was found that a step at the inlet to the dividing header resulted in the shortest tubes.Different ambient conditions were found to affect the inlet steam temperature, the steam flow distribution, heat rejection distribution and the critical dephlegmator length for the single and two-row condensers. There were differences in the steam mass flow distributions for the single and two-row condensers with opposite trends being present in parts of the condenser. The single-row condenser's critical dephlegmator tube lengths were shorter than those of the two-row condenser for the same ambient conditions. Areas of potential backflow change with different ambient conditions and also differ between a single and two-row condenser. The two-row condenser always have an area of potential backflow for the first row at the first condenser fan unit.